Commercial kitchen hood ventilation ducts and exhaust equipment shall comply with the requirements of this section. Commercial kitchen grease ducts shall be designed for the type of cooking appliance and hood served.
506.2 Corrosion ProtectionDucts and exhaust equipment exposed to the outside atmosphere or subject to a corrosive environment shall be protected against corrosion in an approved manner.
506.3 Grease Duct SystemsGrease duct systems shall be designed, constructed and installed in accordance with Sections 506.3.1 through 506.3.13.3.
506.3.1 Grease Duct MaterialsGrease ducts shall be constructed of steel having a minimum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) or stainless steel not less than 0.0450 inch (1.14 mm) (No. 18 gage) in thickness.
Exception: Factory-built commercial kitchen grease ducts listed and labeled in accordance with UL 1978 and installed in accordance with Section 304.1.
506.3.2 Joints, Seams, and Penetrations of Grease DuctsJoints, seams and penetrations of grease ducts shall be made with a continuous liquid-tight weld or braze made on the external surface of the grease duct system.
Exceptions:Grease duct joints shall be butt joints, welded flange joints with a maximum flange depth of 1 /2 inch (12.7 mm) or overlapping duct joints of either the telescoping or bell type. Overlapping joints shall be installed to prevent ledges and obstructions from collecting grease or interfering with gravity drainage to the intended collection point. The difference between the inside cross-sectional dimensions of overlapping sections of duct shall not exceed 1 /4 inch (6.4 mm). The length of overlap for overlapping duct joints shall not exceed 2 inches (51 mm).
506.3.2.2 Grease Duct-to-Hood JointsGrease duct-to-hood joints shall be made with continuous internal or external liquid-tight welded or brazed joints. Such joints shall be smooth, available for inspection, and without grease traps.
Exceptions: This section shall not apply to:Grease duct-to-exhaust fan connections shall be flanged and gasketed at the base of the fan for vertical discharge fans; shall be flanged, gasketed and bolted to the inlet of the fan for side-inlet utility fans; and shall be flanged, gasketed and bolted to the inlet and outlet of the fan for in-line fans. Gasket and sealing materials shall be rated for continuous duty at a temperature of not less than 1,500°F (816°C).
506.3.2.4 Vibration IsolationA vibration isolation connector for connecting a grease duct to a fan shall consist of noncombustible packing in a metal sleeve joint of approved design or shall be a coated-fabric flexible grease duct connector listed and labeled for the application. Vibration isolation connectors shall be installed only at the connection of a grease duct to a fan inlet or outlet.
506.3.2.5 Grease Duct TestA field test shall be performed prior to the use or concealment of any portion of a grease duct system. Grease ducts shall be considered to be concealed where installed in shafts or covered by coatings or wraps that prevent the grease ducts from being visually inspected on all sides. The permit holder shall be responsible to provide the necessary equipment and perform the grease duct leakage test. A light test shall be performed to determine that all welded and brazed joints are liquid tight.
A test shall be performed for the entire grease duct system, including the hood-to-duct connection. The grease duct system shall be permitted to be tested in sections, provided that every joint is tested. For listed factory-built grease ducts, this test shall be limited to duct joints assembled in the field and shall exclude factory welds. The test shall be performed in accordance with either Section 506.3.2.5.1 or 506.3.2.5.2.
506.3.2.5.1 Light TestA duct test shall be performed by passing a lamp, having not less than 1600 lumens, through the entire section of ductwork to be tested. The lamp shall be open so as to emit light equally in all directions perpendicular to the duct walls. A successful test shall be where the light from the lamp is not visible at any point on the exterior of the duct.
506.3.2.5.2 Water Spray TestA duct test shall be performed by simulating a cleaning operation of the interior of the duct. A water pump capable of a flowing outlet pressure of not less than 1,200 psi (8274 kPa) shall be used, along with any necessary hoses and spray nozzles, to apply high-pressure water to the inside surfaces of the duct. A successful test shall be where there is no evidence of cleaning water at any point on the exterior of the duct.
506.3.3 Grease Duct SupportsGrease duct bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of the International Building Code. Bolts, screws, rivets and other mechanical fasteners shall not penetrate grease duct walls.
506.3.4 Air VelocityGrease duct systems shall be designed and installed to provide an air velocity within the grease duct system of not less than 500 feet per minute (2.5 m/s).
Exception: The velocity limitations shall not apply within grease duct transitions utilized to connect grease ducts to differently sized or shaped openings in hoods and fans, provided that such transitions do not exceed 3 feet (914 mm) in length and are designed to prevent the trapping of grease.
506.3.5 Separation of Grease Duct SystemA separate grease duct system shall be provided for each Type I hood. A separate grease duct system is not required where all of the following conditions are met:
Where enclosures are not required, grease duct systems and exhaust equipment serving a Type I hood shall have a clearance to combustible construction of not less than 18 inches (457 mm), and shall have a clearance to noncombustible construction and gypsum wallboard attached to noncombustible structures of not less than 3 inches (76 mm).
Exceptions:Grease duct systems serving a Type I hood shall be constructed and installed so that grease cannot collect in any portion thereof, and the system shall slope not less than 1 /4 unit vertical in 12 units horizontal (2-percent slope) toward the hood or toward a grease reservoir designed and installed in accordance with Section 506.3.7.1. Where horizontal grease ducts exceed 75 feet (22 860 mm) in length, the slope shall be not less than 1 unit vertical in 12 units horizontal (8.3-percent slope).
Exception: Factory-built grease ducts shall be installed at a slope that is in accordance with the listing and manufacturer's installation instructions.
506.3.7.1 Grease Duct Reservoirs Grease duct reservoirs shall:Where a grease duct is large enough to allow entry of personnel, not less than one approved or listed opening having dimensions not less than 22 inches by 20 inches (559 mm by 508 mm) shall be provided in the horizontal sections, and in the top of vertical risers. Where such entry is provided, the grease duct and its supports shall be capable of supporting the additional load, and the cleanouts specified in Section 506.3.8 are not required.
506.3.8.2 Cleanouts Serving In-Line FansA cleanout shall be provided for both the inlet side and outlet side of an in-line fan except where a grease duct does not connect to the fan. Such cleanouts shall be located within 3 feet (914 mm) of the fan duct connections.
506.3.9 Grease Duct Horizontal Cleanouts Cleanouts serving horizontal sections of grease ducts shall: